3.4 General boot parameters
通用启动参数
In addition to the specific parameters for the different station types, the boot parameters for each process station must be configured.
除了不同站类型的特殊参数之外。必须配置每个过程站的启动参数。
Under normal circumstances, the boot parameters should not be modified. Each 正常情况下,不应该修改启动参数。对资源引导参数的每次修改将导致项目版本错误。 必须对资源进行初始化,以使引导参数的修改有效。 |
Basic information that applies to all process stations is described below; the specific dialogs are explained in the following sections:
应用于所有过程站的基本信息的描述于下面。具体的对话框将在下面的章节进行解释。
Parameters of the AC 900F controllers on page 43,
第43页 AC 900F控制器参数
Parameters of the AC 800F and AC 800FR controllers on page 50 and Parameters of the AC 700F controllers on page 59.
第50页 AC 900F和AC 800FR控制器参数,第59页 AC 700F参数。
3.4.1 Process station memory
过程站内存
Although the actually available memory area depends on the type of process station used, the basic allocation is identical for all types. While the operating system is stored in the lower section, the configuration with the object directory and data as well as the redundancy data memory for redundant stations are arranged above. The remaining memory area is available as RAM for current data.
尽管实际可用的内存区域取决于所使用的进程站的类型。所有类型的基本分配都是相同的。操作系统存储在下段,上面布置了对象目录和数据的配置以及冗余站的冗余数据存储器。剩余的内存区域可用作RAM用于当前数据。
The memory of a process station is composed of the following sections: 一个过程站的内存由下面几个部分组成: Memory for the operating system 操作系统的内存 + Memory for the object directory (number of objects * 16 bytes) + 对象目录的内存(对象数量 * 16 字节) + Memory for the configuration data (PRAM) + 配置数据存储器 + Redundancy memory (for redundant stations only) + 冗余存储器(仅用于冗余站) + Memory for working data (RAM) + 工作数据存储器 Using the Boot Parameters 使用启动参数
- Max. objects 最大对象
- Configuration data (PRAM) in kByte 配置数据(PRAM) kByte单位
- Redundancy memory (for redundant stations only) 冗余存储器(仅用于冗余站)
the memory allocation within the process station can be modified. 过程站的内存分配可以修改。 The maximum number of objects is defined by the software architecture. The required minimum value depends on the system configuration. For this reason, it is recommended to start with the default number and to adjust the value accordingly. Bear in mind, that approximately 16 kByte are required for 1000 object entries and that the loaded objects need memory capacity as well. 对象的最大数量由软件架构定义。最小值由系统配置决定。因此,建议从默认值开始,相应的调整该值。记住,1000个对象条目大约需要16 kByte,加载的对象也需要内存容量。 There is no absolute limit in terms of adjustable storage areas. When a limit is reached, this limit can be modified. Such a change will reduce the remaining RAM. 在可调节的存储区域方面没有绝对的限制。当到达极限时,这个限值可以修改。这样的更改将减少剩余的RAM。
If errors occur during loading into the process station, it can be tried to make the project loadable by changing the boot parameters Max. objects and Configuration data (PRAM). 如果在加载过程中发生错误,可尝试通过修改引导参数最大对象和配置数据(PRAM)来使项目可加载。 |
<ps>.PRAM_SIZE | Size of the PRAM area set in the boot parameters of the process station. 在过程站启动参数中设定的PRAM区域大小。 |
<ps>.PRAM_FREE | Proportion of free PRAM 空闲PRAM的比例 |
<ps>.RAM_SIZE | Amount of RAM in use 在用的RAM数量 |
<ps>.RAM_FREE | Proportion of free RAM 空闲RAM的比例 |
Attention should also be paid to the system variables PRAM_Free and RAM_Free after loading. If the PRAM_Free variable has a value of 0, the PRAM_SIZE value must be increased; If the RAM_Free variable has a value of 0, both the PRAM_ SIZE and the maximum number of objects must be reduced. 还要关注加载后的系统变量PRAM_Free和RAM_Free。如果PRAM_Free数值为0,则 PRAM_SIZE 数值需要增加;如果RAM_Free数值为0,PRAM_ SIZE和最大对象数量都必须减少。 |
一个资源上可配置的对象最大数量。1000个对象对应16kB. Configuration data (PRAM) 配置数据(PRAM) Memory area in kByte that is reserved for configuration data. This memory area is cold-start resistant. 为配置数据预留的内存区域,单位为kByte。这个存储区域是耐冷启动的。 Redundancy memory 冗余内存 Memory area in kByte that is reserved for the transfer of redundancy data. 用于传输冗余数据的内存区域,单位为kByte。 Currently required 目前需要 Memory size in byte required by the project for the transfer of redundancy data as calculated by the system. 由系统计算的用于传输冗余数据的项目所需的内存字节大小。
The required redundancy memory is displayed for redundant and plausible process stations only. 所需要的冗余存储器只显示为冗余和合理的过程站。 |
Communication link 通讯连接 |
Required number of interface objects 所需接口对象的数量 |
Telecontrol - symmetric transmission FWK_DEV 遥控 - 对称传输 FWK_DEV |
6 |
Telecontrol - asymmetric transmission master 遥控 - 不对成传输主 FWK_DEV_M |
6 |
Telecontrol - asymmetric transmission slave 遥控 - 不对成传输从 FWK_DEV_S |
5 |
Telecontrol - data transmission FWK_DEV_TCP 遥控 - 数据传输 FWK_DEV_TCP |
6 |
PROFIBUS master PMDEV PROFIBUS 主 PMDEV |
2 |
PROFIBUS master PMEC1 PROFIBUS 主 PMEC1 |
3 |
PROFIBUS master PM930 PROFIBUS 主 PM930 |
4 |
PROFIBUS slave PROFIBUS 从 |
0 |
Modbus master Modbus 主 |
3 |
Modbus slave Modbus 从 |
3 |
Modbus TCP master Modbus TCP 主 |
3 |
Modbus TCP slave Modbus TCP 从 |
1 |
Send 发送 |
1 |
Receive 接收 |
1 |
TCP Send and Receive SR_SRTCP(1) TCP发送和接收 SR_SRTCP |
2 |
(1) not supported with AC 900F and AC 700F 3.4.3 User application tasks 用户应用任务
To ensure bumpless loading of configuration extensions into the process station, memory capacity is reserved during initialization for each configurable user application task. If this flexibility is not required, the reserved memory area can be reduced by the Number of user tasks boot parameter. By reducing the total number of configurable user tasks, additional memory capacity (approx. 12.5 kByte per task) is made available.
为了确保过程站扩展配置无扰动加载,在初始化每个可配置用户任务时保留内存容量。如果不要求这种灵活性,可以通过用户任务引导参数数量来减少预留内存区域。通过减少可配置用户任务的总数,额外的内存容量(约为。每个任务12.5 kByte)可用。
3.4.4 Communication links 通讯连接
A process station can manage up to 10 communication links to operator and gateway stations. The boot parameters Operator stations and Gateway stations define how many communication links to operator and gateway stations are provided for this process station. If the sum of both parameters is below the maximum admissible total number, additional memory capacity for the application is gained. See the Engineering Manual, System Configuration, Project tree.
一个过程站可以管理至多10个到操作员站和网关站的通讯链路。操作员站和网关站启动参数定义了为这个过程站提供了多少到操作员站和网关站的通讯链路。如果两个参数的总和低于最大允许总数,则应用程序获得额外的内存容量。参加《工程手册》,系统配置,项目树。
To calculate the actually required memory capacity of a process station, all 计算过程站实际所需的内存容量,必须考虑所有配置的引导参数。如果超过一个参数被设置为接近最大 数值的值,用于可信性检查的算法将不被完成。
Although no error is reported by the check routine, the loading process cannot be 尽管检查例程没有错误报告,加载过程无法正常执行。控制器可能指示致命错误信号。 在这种情况下,用户必须取出电池来执行冷启动。 |