6.9 Equipotential bonding

等电位连接

ABB AC 900F学习笔记69-Freelance_Mounting_and_Installation_AC_900F_Controller-29

Item No

项目编号

Description

描述

1

Power supply unit for the CPU module *)

CPU模板的电源单元

2

Fuse for the CPU module

CPU模板的保险

3

Power supply unit for the I/O modules *)

IO模板的电源

4

Fuse for the I/O modules *

IO模板的保险

5

Fuses for the relay output contacts see module description

继电器输出连接保险看模板描述

6

0V rail (signal reference potential)

0V排(信号参考电位)

7

Earthing of the 0V rail

0V接地排

8

Switch cabinet earthing

开关柜接地

9

Equipotential bonding line between the switch cabinets, if applicable, at least 16 mm2

开关柜之间的等电位连接线,如果适用,至少16mm2

10

Cable shield earthing

电缆屏蔽接地

*) The use of a common power supply unit is also possible.

也可能是用一个共同的电源装置

 

  • Install sufficiently dimensioned equipotential bonding lines if high potential differences between the system components are present or expected to occur with your specific application
  • 如果系统组件之间存在,或者预计在特定应用中存在高电位差,安装尺寸足够大的等电位连接线。
  • The impedance of the equipotential bonding line should amount to maximum 10% of the shield impedance of shielded signal lines between the same points.
  • 等电位键合线的阻抗应达到相同点之间屏蔽信号线屏蔽阻抗的最大10%
  • The cross-section of the equipotential bonding line must be rated for the maximum compensating current. Experience has shown that a cross-section of 16 mm² is usually sufficient
  • 等电位键合线横截面的额定电流必须达到最大补偿电流。经验表明,16mm²的横截面通常就足够了
  • Equipotential bonding and shielded signal cables should be laid as close as possible to each other to prevent the formation of inductive loops and the risk of interference coupling
  • 等电位键合和屏蔽信号电缆应尽量靠近敷设,防止形成感应回路和干扰耦合的危险
  • Ensure low-impedance connection between equipotential bonding lines and PE.
  • 确保等电位键合线与PE之间的低阻抗连接

 